VENTS AOW 45
Air unit with the water heat exchanger. Maximum capacity - up to 3850 m³/h.
- Description
- Characteristics
- Downloads
- Dimensions
- ADDITIONAL TECHNICAL DATA
- Designation key
- Accessories
Description
Description
APPLICATION | CONTROL AND REGULATION |
|
|
DESIGN | |
|
|
MOUNTING | MOTOR |
|
|
AIR HEATING (COOLING) ADVANTAGES: | |
|
|
VENTS AOW unit greenhouse heating example | VENTS AOW unit garage cooling example |
VENTS AOW unit stock house heating example |
Characteristics
Characteristics
Parameter |
AOW 45 |
Measurement unit |
---|---|---|
Voltage | 230 | V |
Frequency | 50 | Hz |
Fan power | 255 | W |
Fan current | 1.12 | A |
RPM | 1360 | min-1 |
Sound pressure level at 3 m | 58 | dBА |
Maximum heat medium temperature | 100 | °С |
Protection rating | IP 44 | - |
Number of water coil rows | 2 | - |
Weight | 50 | kg |
Insulation class | F | - |
Air reach distance | 16 | mm |
Files archieve
Downloads
Select document type
"Control unit for air heating (cooling) unit with water heat exchanger - UWT series" user's manual 06-2017 (V52-1EN-02) (pdf 383.75Kb)
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
B | 780 | mm |
B1 | 885 | mm |
H | 710 | mm |
H1 | 570 | mm |
L | 380 | mm |
L1 | 300 | mm |
K | G 3/4'' | mm |
ADDITIONAL TECHNICAL DATA
ADDITIONAL TECHNICAL DATA
TECHNICAL DATA FOR HEATING MODE
Model | Air flow [m3/h] | Inlet air temp. [°С] | Temperature difference 90/70 °С | Temperature difference 80/60 °С | Temperature difference 70/50 °С | Temperature difference 60/40 °С | ||||||||||||
Power [kW] | Outlet air temp. [°С] | Water flow [m3/h] | Water pressure loss [kPa] | Power [kW] | Outlet air temp. [°С] | Water flow [m3/h] | Water pressure loss [kPa] | Power [kW] | Outlet air temp. [°С] | Water flow [m3/h] | Water pressure loss [kPa] | Power [kW] | Outlet air temp. [°С] | Water flow [m3/h] | Water pressure loss [kPa] | |||
AOW 45 | 3850 | -15 | 63.0 | 28.4 | 2.81 | 11.9 | 55.6 | 23.3 | 2.41 | 9.7 | 48.1 | 18.1 | 2.09 | 7.6 | 40.4 | 12.8 | 1.80 | 5.7 |
-10 | 59.2 | 31.5 | 2.59 | 10.6 | 51.8 | 26.4 | 2.30 | 8.5 | 44.3 | 21.1 | 1.91 | 6.6 | 36.7 | 15.7 | 1.58 | 4.8 | ||
-5 | 55.4 | 34.6 | 2.41 | 9.4 | 48.0 | 29.3 | 2.09 | 7.4 | 40.6 | 23.9 | 1.80 | 5.6 | 32.9 | 18.5 | 1.40 | 3.9 | ||
0 | 51.6 | 37.5 | 2.30 | 8.3 | 44.3 | 32.2 | 2.02 | 6.4 | 36.9 | 26.8 | 1.58 | 4.7 | 29.2 | 21.3 | 1.30 | 3.2 | ||
5 | 47.9 | 40.4 | 2.09 | 7.3 | 40.6 | 35.0 | 1.80 | 5.5 | 33.2 | 29.5 | 1.51 | 3.9 | 25.6 | 23.9 | 1.12 | 2.5 | ||
10 | 44.3 | 43.2 | 2.02 | 6.3 | 37.0 | 37.8 | 1.58 | 4.6 | 29.6 | 32.2 | 1.30 | 3.2 | 21.9 | 26.4 | 1.01 | 1.9 | ||
15 | 40.6 | 45.9 | 1.80 | 5.4 | 33.4 | 40.4 | 1.51 | 3.8 | 26.0 | 34.8 | 1.12 | 2.5 | 18.1 | 28.8 | 0.79 | 1.3 |
TECHNICAL DATA FOR COOLING MODE
Model | Air flow [m3/h] | Inlet air temp. [°С] | Temperature difference 7/12 °С | |||
Power [kW] | Outlet air temp. [°С] | Water flow [m3/h] | Water pressure loss [kPa] | |||
AOW 45 | 3850 | 35 | 18.0 | 24.9 | 3.1 | 31.8 |
30 | 10.8 | 21.7 | 1.9 | 12.9 | ||
25 | 7.3 | 19.0 | 1.3 | 6.3 | ||
20 | 3.2 | 17.4 | 0.5 | 1.4 |
Designation key
Designation key
Series | Rated power [kW] |
VENTS AOW VENTS AOW1 |
25; 30; 45 |
Accessories
Accessories
Air heating unit model | Control unit | Digital thermostat | Mounting accessories | ||
with sensor display | with LCD display | Mounting angles | Mounting brackets | ||
AOW 25 | UWT-1E | TST-1-300 TSTD-1-300 |
RTS-1-400 RTSD-1-400 |
MKP-AOW | MK-AOW 25 |
AOW1 25 | MK-AOW1 25 | ||||
AOW 30 | MK-AOW 30 | ||||
AOW1 30 | MK-AOW 25* | ||||
AOW 45 | MK-AOW 45 | ||||
AOW1 45 | MK-AOW 30* |
* The cross pieces between the MK-AOW mounting brackets are not applicable in case of AOW1 mounting.