VENTS BOOST 400 (220/60 Hz)
- Description
- Characteristics
- Downloads
- Dimensions
- Overall dimensions of brackets
- Additional technical data
- Designation key
Description
Description
APPLICATION | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
Characteristics
Characteristics
Parameter |
BOOST 400 (220/60 Hz) Min speed |
BOOST 400 (220/60 Hz) Mid speed |
BOOST 400 (220/60 Hz) Max speed |
Measurement unit |
---|---|---|---|---|
Voltage | 1~230 | 1~230 | 1~230 | V |
Frequency | 60 | 60 | 60 | Hz |
Current | 0.73 | 1.00 | 1.40 | A |
Sound pressure level at 3 m distance | 38 | 42 | 43 | dBА |
Power | 146 | 208 | 300 | W |
Maximum air capacity | 513 | 667 | 942 | l/s |
Maximum air capacity | 1846 | 2401 | 3390 | m³/h |
RPM | 1000 | 1320 | 1566 | min-1 |
Max. transported air temperature | -25...+55 | -25...+55 | -25...+55 | °С |
Protection rating | IP X4 | IP X4 | IP X4 | - |
Design | mixed-flow | mixed-flow | mixed-flow | - |
Motor protection rating | IP 20 | IP 20 | IP 20 | - |
Duct diameter | 400 | 400 | 400 | mm |
Casing material | polymer | polymer | polymer | - |
Duct | for round air ducts | for round air ducts | for round air ducts | - |
Mounting | Inline | Inline | Inline | - |
Files archieve
Downloads
Select document type
"VENTS BOOST 315/355/400 / VENTS BOOST 315/355/400 EC" user's manual 12-2021 (V208EN-06) (pdf 1.53Mb)
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
A | 388 | mm |
∅D | 395 | mm |
ØD1 | 441 | mm |
H | 500 | mm |
Overall dimensions of brackets
Overall dimensions of brackets
Model | Dimensions [mm] | ||||
A | A1 | H | H1 | B | |
KM-BOOST 400 | 563 | 624 | 235 | 228 | 180 |
Additional technical data
Additional technical data
Sound-power level, A -filter | Octave-frequency band [Hz] | LpA, 3 m dBA | LpA, 1 m dBA | |||||||||
Hz | Gen. | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||
LwA to inlet | dBA | 71 | 57 | 62 | 66 | 65 | 64 | 61 | 55 | 47 | 51 | 61 |
LwA to outlet | dBA | 73 | 57 | 65 | 63 | 67 | 68 | 63 | 59 | 51 | 52 | 62 |
LwA to environment | dBA | 64 | 45 | 52 | 53 | 57 | 60 | 54 | 48 | 38 | 43 | 53 |
Designation key
Designation key
Series | Air duct diameter [mm] | Options |
VENTS BOOST | 150; 160; 200; 250; 355; 400 | Un: speed controller with an electronic thermostat and external temperature sensor fixed R: power cord with a mains plug V: step speed controller P: built-in smooth speed controller |