VENTS CO2-1
- Description
- Characteristics
- Downloads
- Dimensions
Description
Description
APPLICATION
|
MOUNTING AND POWER SUPPLY
|
Characteristics
Characteristics
Parameter |
CO2-1 |
Measurement unit |
---|---|---|
Power supply/ power consumption | 24 VAC (50/60 Hz ± 10%), 24 VDC/1.6 W Max | W |
Gas detection analyzer | Non-dispersive infrared detector (NDIR) with self-calibration system | - |
CO2 measuring range | 0–2,000 ppm (parts per million) | - |
Accuracy at 25°С (77°F), 2000 ppm | ±30 ppm + 3 % of reading | - |
Response time | max. 2 min | - |
Warm up time for each turning-on | 2 hours (first time), 2 minutes (operation) | - |
Analogue output | t 0–10VDC (default), 4–20mA selectable by jumpers | - |
On/Off output | 1X2A switch load Four set points selectable by jumpers | - |
6 LED lights for CO2 concentration indication | 1st green indicator lights when CO2 concentration is below 600 ppm;, 1st and 2nd green indicators light when CO2 concentration is 600–800 ppm;, 1st yellow indicator lights when CO2 concentration is 800–1200 ppm;, 1st and 2nd yellow indicators light when CO2 concentration is 1200–1400 ppm;, 1st red indicator lights when CO2 concentration is 1400–1600 ppm;, 1st and 2nd red indicators light when CO2 concentration is above 1600 ppm | - |
Operating conditions/ storage recommendations | 0–50 °C; 0–95 % RH non condensing/0–50 °C | - |
Weight/ Dimensions | 0.120 kg/100 mm х 80 mm х 30 mm | kg |
Mounting | outdoor mounting | - |
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|
Similar products