MediVent BR 15х1 T
- Description
- Characteristics
- Downloads
- Dimensions
- Recommended reference areas
Description
Description
FIRST TOTALLY SAFE UV AIR STERILIZERS MEDIVENT BR 7Х1 AND MEDIVENT BR 7Х2, MEDIVENT BR 15Х1 AND MEDIVENT BR 15Х2 UV AIR STERILIZERS |
|||||||||||||||||||||
|
|
||||||||||||||||||||
WHY BUY MEDIVENT BR AIR RECIRCULATION UNIT? |
|||||||||||||||||||||
|
|||||||||||||||||||||
APPLICATION |
|||||||||||||||||||||
Characteristics
Characteristics
Parameter |
MediVent BR 15х1 T |
Measurement unit |
---|---|---|
Voltage | 230 | V |
Current | 0.133 | A |
Frequency | 50 | Hz |
Sound pressure level at 3 m distance | 29 | dBА |
Power | 21 | W |
Number of lamps | 1 | - |
Lamp type | OSRAM HNS 15 W G13 | - |
Rated service life of the lamp | 9000 | h |
UV wavelength | 254 | nm |
UV power | 4.9 | W |
Weight | 4.81 | kg |
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
B | 124 | mm |
L | 735 | mm |
H | 128 | mm |
Recommended reference areas
Recommended reference areas
Model | Volume of the room served by one UV air sterilizer [m3] | Floor area of the room served by one UV air sterilizer with a ceiling height of 2.7 m [m2] | ||||
Residential spaces, schools, kindergartens, children's playrooms, etc. | Medical and dental offices, general medical wards, etc. | Resuscitation and dressing wards, pharmaceutical plants, bacteriological and virological laboratories | Residential spaces, schools, kindergartens, children's playrooms, etc. | Medical and dental offices, general medical wards, etc. | Resuscitation wards, dressing rooms, pharmaceutical shops, bacteriological and virological laboratories | |
MediVent BR 7х1 | 21 | 16 | 11 | 8 | 6 | 4 |
MediVent BR 7х2 | 42 | 32 | 21 | 16 | 12 | 8 |
MediVent BR 15х1 | 54 | 42 | 28 | 20 | 16 | 10 |
MediVent BR 15х2 | 109 | 85 | 55 | 40 | 31 | 20 |
Depending on the legal requirements in your country, the area or volume of rooms to be served by a single air recirculation unit may vary significantly.
Before using air circulation units, study the possibility of using them in accordance with the laws of your country.