Login

Privacy Policy (GDPR)
Authorization
Not registered yet? Take advantages of registration:
Products saving in a binding to the projects
Product consultation from our experts - Online
Registration
Signup
By using this form, you confirm that you have read the site terms of use Terms of use and completely accept the terms of use

VENTS VA 02

  • Description
  • Characteristics
  • Downloads
  • Dimensions
  • Additional diagrams
  • Legend
Description
Description
DESCRIPTION
  • The unit VA is a fan-filter block enclosed in a compact sound-insulated casing.

  • The VA unit provides high pressure combined with low energy demand due to the impeller with backward curved blades.

  • The unit is suitable for supply and exhaust ventilation applications.
CASING
  • Steel casing covered with aluzinc coating internally filled with 50 mm heat- and sound-insulating layer made of mineral wool.

FAN
  • The units are equipped with a high-pressure radial fan directly driven from the external rotor motor with backward curved blades.

  • The fan motor has integrated thermal contacts for connection to an external protecting device.
FILTER
  • The unit is suitable for use both with and without filter as a simple fan. The replaceable filter block is an optional item and is not included into the unit delivery set.

  •  All the units may be equipped with a replaceable G4 panel filter, refer Accessories.
MOUNTING
  • The unit is mounted to the air duct in any position.

  • The unit is suitable for installation in utility and main premises behind the false ceiling, in the recess or directly in the room.

  • The fan electric contacts are leaded to the terminal block located in the terminal box.

ACCESSORIES TO SUPPLY UNITS:  

SF

Type Replaceable filter Filter type
VА 01 SF PА/VA 01 Е G4 panel filter
VА 02 SF PА/VA 02 Е G4 panel filter
VА 03 SF PА/VA 03 Е G4 panel filter
VА 04 SF VA 04 Е G4 panel filter

ACCESSORIES

 
  • The fan speed is controlled by the external triac, autotransformer or frequency three phase speed controller, refer RSAVFED).

  • To disable uncontrollable air flow when the fan is off and in case of power failure it is recommended to install the air damper with a return spring from outside behind the unit.

  • For attenuation of sound generated by the fan it is recommended to install the duct silencer (refer SR) from inside before the unit.

  • For vibration absorbing it is recommended to install the flexible anti-vibration connectors (refer VVG) on both sides of the unit.

  • For control of the filter clogging degree it is recommended to install the differential pressure switch (refer DTV 500).

Characteristics
Characteristics
Parameter VA 02
Measurement unit
Frequency 50 Hz
Phase 3 ˜
Engine Type 380В / 50Гц -
Voltage 400 V
Maximum fan power Maximum fan power 620 W
Fan current Fan current 1.05 A
Maximum air capacity 2700 m³/h
RPM 2690 min-1
Noize level at 3 m 54 dBА
Casing material aluzinc -
Maximum transported air temperature Maximum transported air temperature -25 +45 °С
Heating without heating -
Insulation 50 mm, mineral wool -
Width 500 mm
Connected air duct size 500х300 mm
Weight 38 kg
Height 300 mm
Heater type Heater type none -
Unit size Unit size 02 -
Duct for rectangular air ducts -
Type Type вытяжная -
Files archieve
Downloads
Select document type
  • Advertising and printing products
  • Certificates
  • Technical documentation
Name
"VENTS VA" product description 02-2016 (pdf 149.53Kb)
Download high quality image "VENTS VA (ErP 2016, 2018)" (psd 3.93Mb)
Download image "VENTS VA (ErP 2016, 2018)" for your website (png 296.17Kb)
Dimensions
Characteristics
VENTS VA 02
Parameter Value Measurement unit
B 500 mm
B1 520 mm
B2 689 mm
B3 646 mm
H 300 mm
H1 320 mm
H2 450 mm
L 665 mm
L1 627 mm
Additional diagrams
Additional diagrams
Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 75 56 68 72 57 55 58 61 57
LwA to outlet dBA 81 57 71 80 74 70 69 69 62
LwA to environment dBA 62 37 51 62 52 39 36 39 34

Legend
Legend
Series   Unit standard size
VENTS VA
  01; 02; 03; 04
Share your opinion

Questionnaire
Where have you learned about us?