VENTS VCUN 250x127-2,2-4
- Description
- Characteristics
- Downloads
- Dimensions
- Additional diagrams
- Designation key
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
SELECTION TABLE FOR ACCESSORIES: | |
Type |
Rubber |
Spring-loaded |
Flange | Flexible connector | Grille |
VCUN 140х74-0,25-4 | VVCr 8 | VVCp 8 | FVC 140 | VVG 140 VVG-VCUN 92х95 |
RVC 140 |
VCUN 140х74-0,37-2 | |||||
VCUN 160x74-0,55-4 | FVC 160 | VVG 160 VVG-VCUN 106х104 |
RVC 160 | ||
VCUN 160х74-0,75-2 | |||||
VCUN 180х74-0,55-4 | FVC 180 | VVG 180 VVG-VCUN 120х114 |
RVC 180 | ||
VCUN 180х74-1,1-2 | |||||
VCUN 200х93-0,55-4 | FVC 200 | VVG 200 VVG-VCUN 134х129 |
RVC 200 | ||
VCUN 200х93-1,1-2 | |||||
VCUN 225х103-1,1-4 | FVC 225 | VVG 225 VVG-VCUN 151х141 |
RVC 225 | ||
VCUN 225х103-2,2-2 | |||||
VCUN 240x114-2,2-4 | VVCr 16 | VVCp 16 | FVC 240 | VVG 240 VVG-VCUN 161х156 |
RVC 240 |
VCUN 240х114-3,0-2 | |||||
VCUN 250х127-1,5-6 | FVC 250 | VVG 250 VVG-VCUN 168х166 |
RVC 250 | ||
VCUN 250х127-2,2-4 | |||||
VCUN 250х127-5,5-2 | |||||
VCUN 280х127-1,5-6 | FVC 280 | VVG 280 VVG-VCUN 189х196 |
RVC 280 | ||
VCUN 280х127-2,2-4 | |||||
VCUN 280х127-5,5-2 | |||||
VCUN 315х143-2,2-6 | VVCr 26 | VVCp 26 | FVC 315 | VVG 315 VVG-VCUN 213х216 |
RVC 315 |
VCUN 315х143-4,0-4 | |||||
VCUN 355х143-2,2-6 | FVC 355 | VVG 355 VVG-VCUN 241х214 |
RVC 355 | ||
VCUN 355х143-4,0-4 | |||||
VCUN 400х183-1,5-8 | VVCr 35 | VVCp 35 | FVC 400 | VVG 400 VVG-VCUN 272х268 VVG-VCUN 272х289 |
RVC 400 |
VCUN 400х183-2,2-6 | |||||
VCUN 400х183-5,5-4 | |||||
VCUN 450х203-3,0-8 | VVCr 50 | VVCp 50 | FVC 450 | VVG 450 VVG-VCUN 306х315 |
RVC 450 |
VCUN 450х203-4,0-6 | |||||
VCUN 450х203-11,0-4 | |||||
VCUN 500х229-5,5-8 | VVCr 75 | VVCp 75 | FVC 500 | VVG 500 VVG-VCUN 341х353 |
RVC 500 |
VCUN 500х229-7,5-6 | |||||
VCUN 500х229-11,0-4 |
Scroll orientation (view on the intake side)
|
Right scroll orientation |
Left scroll orientation |
|
|
|
|
Anti-vibration mount VVCr | Anti-vibration mount VVCp |
VENTS VCUN fan catering ventilation example |
Parameter |
VCUN 250x127-2,2-4 |
Measurement unit |
---|---|---|
Engine Type | 380В / 50Гц | - |
Voltage | 400 | V |
Frequency | 50 | Hz |
Sound pressure level at 3 m distance | 78 | dBА |
Maximum transported air temperature | °С | |
Protection rating | IP 54 | - |
Weight | 32.2 | kg |
Number of poles | 4 | - |
Impeller diameter | 250 | mm |
Impeller width | 127 | mm |
Parameter | Value | Measurement unit |
---|---|---|
∅D | 250 | - |
∅d | 10 | mm |
H2 | 168 | mm |
B | 431 | mm |
H3 | 292 | mm |
M | 300 | - |
I | 373 | - |
H | 594 | mm |
H1 | 202 | mm |
K | 355 | - |
S | 125 | - |
L | 473 | mm |
∅d1 | 12 | - |
L1 | 202 | mm |
L2 | 166 | mm |
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to environment | dBA | 70 | 56 | 71 | 77 | 74 | 81 | 82 | 80 | 73 |
Series | Impeller diameter, mm | Impeller width, mm | Motor modification | Scroll orientation* | Casing rotation angle* | ||||
Power [kW] | Number of poles | ||||||||
VENTS VCUN | 140; 160; 180; 200; 225; 250; 280; 315; 355; 400; 450; 500 | х | 74; 93; 103; 127; 143; 183; 203; 229 | – | 0.25; 0.37; 0.55; 0.75; 1.1; 1.5; 2,2; 3; 4; 5.5; 7.5; 11 | – | 2; 4; 6; 8 | R: right side; L: left side |
0; 45; 90; 135; 180; 225; 270; 315 |
*Standard casing modification PR90