VENTS VK 100 Duo
Inline centrifugal fan in plastic casing with the air flow up to 264 m³/h.
3D model
Gallery
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional characteristics
- Designation key
- Video
Description
Description
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING |
VK fan kitchen exhaust ventilation example |
|
|
THE FAN WITH ELECTRONIC TEMPERATURE AND CONTROL MODULE (U OPTION). | |
|
|
CONTROL LOGIC OF THE FAN WITH THE ELECTRONIC TEMPERATURE AND SPEED CONTROL MODULE | |
|
|
There are two switch delay patterns for various cases: | |
|
|
Example for temperature sensor delay pattern: | Example for timer delay pattern: |
|
|
|
|
↓ | ↓ |
|
|
↓ | ↓ |
|
|
↓ | ↓ |
|
|
↓ | ↓ |
|
|
↓ | |
|
|
↓ | |
|
|
↓ | |
|
|
|
Characteristics
Characteristics
Parameter |
VK 100 Duo Min. speed |
VK 100 Duo Max. speed |
Measurement unit |
---|---|---|---|
Frequency | 50 | 50 | Hz |
Phase | 1 | 1 | ˜ |
Voltage | 230 | 230 | V |
Power | 45 | 57 | W |
Current | 0.21 | 0.25 | A |
Sound pressure level at 3 m distance | 38 | 38 | dBА |
Maximum air capacity | 157 | 264 | m³/h |
EC motor | no | no | - |
RPM | 1820 | 2440 | min-1 |
Protection rating | IP X4 | IP X4 | - |
Design | centrifugal | centrifugal | - |
Duct diameter | 100 | 100 | mm |
Casing material | plastic | plastic | - |
Width | 270 | 270 | mm |
Weight | 2.01 | 2.01 | kg |
Height | 250 | 250 | mm |
SEC Class | D | D | - |
Outdoor mounting | no | no | - |
Sound-insulated casing | no | no | - |
Duct | for round air ducts | for round air ducts | - |
Type | exhaust, supply | exhaust, supply | - |
Mounting | Inline | Inline | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 100 | mm |
ØD1 | 250 | mm |
B | 270 | mm |
L | 230 | mm |
L1 | 30 | mm |
L2 | 27 | mm |
L3 | 30 | mm |
Additional characteristics
Additional characteristics
A-weighted sound pressure level | Octave-frequency band [Hz] | Sound pressure level @ 3 m, A-filter applied | Sound pressure level @ 1 m, A-filter applied | |||||||||
Hz | Gen. | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | LpA, 3 m [dBA] | LpA, 1 m [dBA] | |
LwA to inlet | dBA | 79 | 57 | 71 | 77 | 69 | 64 | 60 | 54 | 43 | 58 | 68 |
LwA to outlet | dBA | 79 | 64 | 72 | 77 | 69 | 61 | 57 | 53 | 42 | 58 | 68 |
LwA to environment | dBA | 58 | 27 | 46 | 48 | 53 | 54 | 50 | 41 | 32 | 38 | 48 |
Designation key
Designation key
Series | Duct diameter [mm] | Options | |
VENTS VK | S: high-powered motor | 100; 125; 150*; 200; 250; 315 |
Q: low-powered motor. Duo: double-speed motor. U: speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Temperature-based operation logic. Un: speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. Temperature-based operation logic. U1: speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Timer-based operation logic. U1n: speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. Timer-based operation logic. P: built-in smooth speed controller and power cord with IEC C14 electric plug. V: built-in speed switch (for models with double-speed motors). R: power cord with IEC C14 electric plug. |
* VK 150 model is compatible with the air ducts both Ø 150 and 160 mm
Video
Video
Accessories