VETNS VKF 4E 550
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- ADDITIONAL TECHNICAL DATA
- DESIGNATION KEY
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
Parameter |
VKF 4E 550 50 Hz |
VKF 4E 550 60 Hz |
Measurement unit |
---|---|---|---|
Phase | 1 | 1 | ˜ |
Voltage | 230 | 230 | V |
Frequency | 50 | 60 | Hz |
Sound pressure level at 3 m distance | 62 | 63 | dBА |
Power consumption | 550 | 654 | W |
Maximum air capacity | 8800 | 8970 | m³/h |
RPM | 1300 | 1580 | min-1 |
Protection rating | IP X4 | IP X4 | - |
Weight | 13.9 | 13.9 | kg |
Current | 2.55 | 2.88 | A |
- Selection method:
- Air flow:
- Pressure:
- Air flow: --
- Pressure: ---
Parameter | Value | Measurement unit |
---|---|---|
∅D | 565 | mm |
∅d | 11.5 | mm |
ØD2 | 636 | mm |
B | 660 | mm |
L | 230 | mm |
∅D1 | 605 | mm |
Sound-power level, A-weighted | Gen. | Octave-frequency band [Hz] | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||
dBA | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to environment | dBA | 83 | 52 | 64 | 71 | 77 | 78 | 77 | 72 | 64 | 62 | 72 |
ŋ, [%] | MC | EC | N | VSD | [kW] | [A] | [m3/h] | [Pа] | [n/min-1] | SR |
34.7 | A | Static | 42.6 | No | 0.581 | 2.64 | 5919 | 120 | 1240 | 1 |
Series and modification | Motor modification | Dimension type | |
Number of poles | Phase | ||
VENTS VKF: mounting into a vent duct |
2 |
E: single phase D: three phase |
200; 250; 300; 350; 400; 450; 500; 550; 630, 710, 800 |
ErP data | |
Overall efficiency | ŋ, [%] |
Measurement category | MC |
Efficiency category | EC |
Efficiency grade | N |
Variable speed drive | VSD |
Power | [kW] |
Current | [A] |
Air flow | [m3/h] |
Static pressure | [Pа] |
Speed | [n/min-1] |
Specific ratio | SR |