VENTS VKP 100


Inline centrifugal fan. Maximum capacity - 250 m3/h.

  • Description
  • Characteristics
  • Capacity diagram
  • Downloads
  • Dimensions
  • Additional diagrams
  • Legend
Description
Description
APPLICATIONS
  • Supply and exhaust ventilation systems for various premises with the limited mounting space. 
  • Suitable for connection with Ø 100 and up to 160 mm round ducts.
DESIGN
  • The fan casing is made of steel with polymeric coating. 
  • The removable cover provides easy access to the motor, thus ensuring easy mounting as well as the fan and the air ducts maintenance without dismounting.
MOTOR
  • The centrifugal impeller with backward curved blades is powered by means of the single-phase motor with external rotor and overheating protection with automatic restart. 

  • The motor is equipped with ball bearings for long service life designed for at least 40 000 hours.
  • For precise features, safe operation and low noise, each turbine is dynamically balanced while assembly.
  • Motor protection rating IP 44.
SPEED CONTROL
  • Smooth or step speed control is performed with the thyristor or autotransformer controller. 
  • Several fans can be connected to one controller in case the total power and operating current do not exceed the rated controller values.
MOUNTING
  • Mounting at any angle to wall is performed with fastening bracket supplied with the unit.
  • The fan is powered through the external terminal box.
  • Electric supply and mounting shall be performed in compliance with the manual and wiring diagram on the terminal box.
VENTS VKP fan office ventilation example
Characteristics
Characteristics
Parameter VKP 100
50 Hz
VKP 100
60 Hz
Measurement unit
Number of intake spigots 1 1 -
Voltage 1~ 220-240 1~ 220-240 V
Frequency 50 60 Hz
Sound pressure level at 3 m distance 47 48 dBА
Power consumption 58 79 W
Maximum air capacity 240 250 m³/h
Current 0.26 0.35 A
Max. transported air temperature -25 +50 -25 +50 °С
RPM 2500 2730 min-1
Protection rating IP X4 IP X4 -
Design centrifugal centrifugal -
Weight 4.65 4.65 kg
Duct diameter 100 100 mm
Casing material polymer coated steel polymer coated steel -
SEC Class C C -
Duct for round air ducts for round air ducts -
Type , , -
Mounting wall mounting, Inline wall mounting, Inline -
Capacity diagram
Capacity diagram
  • Selection method:
  • Air flow:
  • Pressure:
Operating point
  • Air flow: --
  • Pressure: ---
Files archieve
Downloads
Select document type
  • Advertising and printing products
  • Certificates
  • Technical documentation
Name
"VENTS VKP, VKP mini" user's manual 05-2022 (V17EN-06) (pdf 1.66Mb)
"VENTS VKP (for round ducts)" product description 03-2021 (pdf 1.78Mb)
Download high quality image "VENTS VKP (ErP 2016, 2018)" (psd 3.66Mb)
Download image "VENTS VKP (ErP 2016, 2018)" for your website (png 236.6Kb)
Dimensions
Characteristics
VENTS  VKP 100
Parameter Value Measurement unit
∅D 99 mm
B 252 mm
H 133 mm
L 420 mm
L2 321 mm
Additional diagrams
Additional diagrams
Sound-power level Octave-frequency band [Hz]
  Hz General 63 125 250 500 1000 2000 4000 8000
LwA to inlet dBA 58 53 55 53 51 51 54 53 48
LwA to outlet dBA 66 51 51 54 56 64 61 56 52
LwA to environment dBA 51 38 37 42 43 46 41 40 32
Legend
Legend
Series Exhaust spigot diameter, mm Intake spigot diameter, mm Number of intake spigots
VENTS VKP
100; 125; 150; 160 100; 125; 150; 160 _(by default) 1; 2; 4