Login

Privacy Policy (GDPR)
Authorization
Not registered yet? Take advantages of registration:
Products saving in a binding to the projects
Product consultation from our experts - Online
Registration
Signup
By using this form, you confirm that you have read the site terms of use Terms of use and completely accept the terms of use

VENTS VOK 2E 250*


Axial roof fan with the air capacity up to 1150 m³/h in the steel casing with the horizontal exhaust of air.

  • Description
  • Characteristics
  • Capacity diagram
  • Downloads
  • Dimensions
  • Legend
Description
Description
APPLICATIONS
  • Exhaust ventilation system for various premises for roof mounting.

  • Compatible with Ø 200 to 500 mm round air ducts.
DESIGN
  • The fan casing is made of steel with polymeric coating.

 
MOTOR
  • The impellers are powered with two- or four-pole, singlephase asynchronous motors with external rotor and built-in thermal overheating protection with automatic restart depending on the model.

  • Ball bearings in the motor ensure long service life.

  • Motor protection rating IP 24.

SPEED CONTROL
  • Both smooth or step speed control is performed by means of the thyristor or autotransformer controller.

  • Several fans can be connected to one controller under condition that the total power and operating current do not exceed the rated controller values.

MOUNTING
  • The fan is mounted on the roof directly above the ventilating duct or shaft and is firmly fixed to the flat surface by means of a connecting plate.

  • While mounting VOK fans directly onto the flat roof a supporting block shall be provided to prevent water and snow drops into the vent of the ventilation shaft.

  • Electrical connection and installation shall be performed in compliance with the manual and circuit diagram on the terminal box.

Characteristics
Characteristics
Parameter VOK 2E 250*
50 Hz
VOK 2E 250*
60 Hz
Measurement unit
Phase 1 1 ˜
Voltage 230 230 V
Frequency 50 60 Hz
Sound pressure level at 3 m distance 60 61 dBА
Power consumption 80 91 W
Maximum air capacity 1050 1150 m³/h
RPM 2400 2990 min-1
Transported air temperature -30...+60 -30...+50 °С
Protection rating IP 24 IP 24 -
Design axial axial -
Weight 7 7 kg
Duct diameter 250 250 mm
Number of poles 2 2 -
Casing material polymer coated steel polymer coated steel -
Sound-insulated casing no no -
Duct for round air ducts for round air ducts -
Type exhaust exhaust -
Mounting for roof for roof -
Current 0.4 0.42 A
Capacity diagram
Capacity diagram
  • Selection method:
  • Air flow:
  • Pressure:
Operating point
  • Air flow: --
  • Pressure: ---
Files archieve
Downloads
Select document type
  • Advertising and printing products
  • Certificates
  • Technical documentation
Name
"VKV, VKH, VKV EC, VKH EC, VKMK, VKMKp, VOK, VOK1" user's manual 01-2021 (V12EN-09) (pdf 1.96Mb)
"VENTS VOK" product description 03-2021 (pdf 647.26Kb)
Download high quality image "VENTS VOK (ErP 2015, 2016, 2018)" (psd 3.85Mb)
Declaration of сonformity "VOK, VOK1" (pdf 1.65Mb)
"Roof fans accessories" product description 02-2016 (pdf 132.53Kb)
Download image "VENTS VOK (ErP 2015, 2016, 2018)" for your website (png 291.07Kb)
Dimensions
Characteristics
VENTS VOK 2E 250*
Parameter Value Measurement unit
∅D 262 mm
Ø D1 405 mm
H 280 mm
L 425 mm
L1 330 mm
Legend
Legend
Series Motor modification Impeller diameter
Number of poles Phase
VENTS VOK 2, 4 E: single phase 200; 250; 300; 350

 

ErP data  
Overall efficiency η, [%]
Measurement category MC
Efficiency category EC
Efficiency grade N
Variable speed drive VSD
Power [kW]
Current [A]
Air flow [m3/h]
Static pressure [Pa]
Speed [n/min-1]
Specific ratio SR
Share your opinion

Questionnaire
Basic parameter for domestic fan selection