VENTS VS 400 4D (Υ)


Inline centrifugal sound- and heat-insulated duct fans with back-curved impeller blades. Maximum capacity - 3525 m3/h. Υ - star connection.

  • Description
  • Characteristics
  • Downloads
  • Dimensions
  • Additional diagrams
  • Designation key
  • BIM
Description
Description
APPLICATIONS
  • Supply and exhaust ventilation systems for various premises with high noise level requirements.

  • The VS fan design enables to assemble various ventilation configurations due to changeable positions of the removable panels.

  • Such design enables air supply in all directions, both linearly and at the angle 90 °C.

  • The aluzinc casing with high corrosion-resistant properties and heat-insulating material allows outdoor installation of the fan.

  • The fans may be integrated into an assembled supply ventilation system.

DESIGN
  • The fan casing is made of aluminium frame, fastened with aluminium bends and removable double-skinned aluzinc panels, heat- and sound-insulated with 20 mm non-combustible mineral wool.

  • The connecting pipes that also serve as vibration absorbing connectors are available with round and square sections.

  • The round pipes are fitted with rubber sealing rings. 

  • The connecting pipes are not included into the delivery set and are available upon separate order! 

MOTOR
  • 4- or 6-pole asynchronous external rotor motor and centrifugal impeller with backward curved blades.

  • The motors are equipped with overheating protection, which is connected to the external protection device (i.e., the model VS 355-4E has thermal switches with automatic restart).

  • The specially greased ball bearing motor ensures low noise and maintenance-free operation.
SPEED CONTROL
  • Smooth or step speed control with a thyristor or autotransformer speed controller.

  • Speed control is adjusted by the supply voltage regulation.

  • Air flow is regulated by the motor speed.

  • Several fans may be connected to one speed controller provided that the total power and operating current do not exceed the rated speed controller parameters.

MOUNTING
  • Inline fans are designed for connection to rectangular or round air ducts with a flexible connector of respective cross section.

  • The fan are designed for inline mounting.

  • While connecting the fan to flexible connectors, provide its fixing to a building with supports, suspension or fixing bracket.

  • The fan is suitable for any mounting position, on condition that the pointer on the fan casing matches the air motion direction in the system.

  • While mounting the fan provide enough access for its servicing.

OFFERED OPTIONS FOR FANS
VPG VVG KN-VS VPR-VS
       
Options Dimensions [mm]
VPG VVG KN-VS VPR-VS A A1 B B1 C ØD E F G
VPG 500/355 VVG 500х500 KN-VS 315-355 VPR-VS 315-355 490 478 470 458 445 355 458 225 600
VPG 670/400 VVG 670х670 KN-VS 400-500 VPR-VS 400-500 660 648 640 628 615 400 628 321 770
VPG 670/450 660 648 640 628 615 400 628 321 770
VPG 670/500 660 648 640 628 615 400 628 321 770
VPG 800/560 VVG 800х800 KN-VS 560-630 VPR-VS 560-630 790 778 770 758 745 560 758 421 900
VPG 800/630 790 778 770 758 745 560 758 421 900
VPG 1000/710 VVG 1000х1000 KN-VS 710 VPR-VS 710 990 978 970 958 945 710 758 421 900
   
VENTS VS fan gym ventilation example VENTS VS fan office ventilation example
Characteristics
Characteristics
Parameter VS 400 4D (Υ)
60 Hz
VS 400 4D (Υ)
60 Hz
Measurement unit
Highpowered motor Highpowered motor no no -
Phase 3 3 ˜
Voltage 400 Y 400 Y V
Frequency 50 60 Hz
Sound pressure level at 3 m distance 47 49 dBА
Power consumption 385 515 W
RPM 1235 1220 min-1
Current 0.7 0.93 A
Max. transported air temperature -40 +80 -40 +40 °С
Protection rating IP X4 IP X4 -
Maximum air flow capacity at cross directed Maximum air flow capacity at cross directed 3340 3525 m³/h
Maximal air flow capacity at straight directed Maximal air flow capacity at straight directed 3110 3290 m³/h
Design centrifugal centrifugal -
Weight 39 39 kg
Duct diameter 400 400 mm
Number of poles 4 4 -
Sound- and heat-insulated casing yes yes -
Casing material aluzinc aluzinc -
Duct for square air ducts, for round air ducts for square air ducts, for round air ducts -
Type supply and exhaust supply and exhaust -
Mounting Inline Inline -
Files archieve
Downloads
Select document type
  • Advertising and printing products
  • Certificates
  • Technical documentation
Name
"VENTS VS, VS EC" user's manual 08-2023 (V19EN-06) (pdf 3.99Mb)
"VENTS VS" product description 05-2022 (pdf 1.43Mb)
Download high quality image "VENTS VS (ErP 2015, 2016, 2018)" (psd 3.87Mb)
Declaration of сonformity "VS" (pdf 1.63Mb)
Download image "VENTS VS (ErP 2015, 2016, 2018)" for your website (png 276.86Kb)
Dimensions
Characteristics
VENTS  VS 400 4D (Υ)
Parameter Value Measurement unit
A 690 mm
Additional diagrams
Additional diagrams
Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 73 57 63 64 67 68 62 59 52
LwA to outlet dBA 74 60 63 65 69 66 67 61 51
LwA to environment dBA 54 43 44 49 50 51 47 42 36

 

ƞ, [%]   MC   EC   N   VSD   [kW]   [A]   [m3/h]   [Pa]   [RPM]   SR
3~ 400Y – star connection
41.0   А   Static   56.5   No   0.335   0.56   1789   271   1390   1

 

 

Designation key
Designation key
Series Impeller diameter Motor
Polarity Phase
VENTS VS 355; 400; 450; 500; 560; 630; 710 S: high-powered motor 4, 6 E:single phase
D: three phase
BIM
BIM

Share your opinion