VENTS VUE 250 V EC A11
Air handling unit in heat- and sound-insulated casing. Air flow up to 290 m³/h. Heat recovery efficiency up to 90 %.
- Description
- Characteristics
- Downloads
- Dimensions
- Additional technical data
- Designation key
- Accessories
Description
Description
DESCRIPTION | |
|
|
FILTER | FANS |
|
|
HEAT EXCHANGER | |
|
|
CASING | BYPASS |
|
|
CONTROL AND AUTOMATION | |
|
|
MOUNTING | |
|
|
UNIT DESIGN* | |
* The unit design differs depending on the model |
|
APPLICATION OPTIONS | |
Characteristics
Characteristics
Parameter |
VUE 250 V EC A11 |
Measurement unit |
---|---|---|
Frequency | 50/60 | Hz |
Phase | 1 | ˜ |
Voltage | 230 | V |
Maximum unit power | 115 | W |
Sound pressure level at 3 m distance | 25 | dBА |
Air capacity | 290 | m³/h |
RPM | 2050 | min-1 |
Maximum unit current | 0.9 | A |
Heat recovery efficiency | 78...90 | % |
Transported air temperature | -25 ... +40 | °С |
Weight | 51 | kg |
Casing material | painted steel | - |
Insulation | 30 mm mineral wool | - |
Filter: extract | G4 | - |
Filter: supply | G4, F7 | - |
Connected air duct size | 160 | mm |
Heat exchanger type | counter-flow | - |
Heat exchanger material | enthalpy | - |
SEC Class | A | - |
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 159 | mm |
B | 489 | mm |
H | 881 | mm |
L | 567 | mm |
Additional technical data
Additional technical data
A-weighted sound power level | Gen. | Octave-frequency band [Hz] | LpA, 3 m [dBA] | LpA, 1 m [dBA] | ||||||||
dBA | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to supply air inlet | 52 | 28 | 46 | 50 | 41 | 36 | 33 | 36 | 29 | |||
LwA to supply air outlet | dBA | 61 | 33 | 53 | 60 | 48 | 38 | 37 | 43 | 36 | ||
LwA to exhaust air inlet | dBA | 52 | 28 | 46 | 50 | 42 | 36 | 33 | 35 | 30 | ||
LwA to exhaust air outlet | dBA | 62 | 32 | 51 | 61 | 49 | 37 | 37 | 42 | 33 | ||
LwA to environment | dBA | 45 | 25 | 41 | 42 | 35 | 32 | 28 | 27 | 22 | 25 | 35 |
Calculation of air temperature downstream of the heat exchanger:
t = toutd + khr * (textr - toutd) / 100,
where
toutd - outdoor air temperature [°C]
textr - extract air temperature [°C]
khr - heat exchanger efficiency (according to the diagram) [%]
Designation key
Designation key
Series | Rated air flow [m3/h] | Spigot orientation | Casing design | Bypass | Motor type | Control |
VUT: ventilation with heat recovery VUE: ventilation with energy recovery |
160; 250; 300; 350; 550 | V: vertical | _: default value 1: casing modification 2: 20 mm insulation |
_: without a bypass B: with a bypass |
ЕС: synchronous electronically commutated motor | А11 |
Accessories
Accessories
Model | G4 supply filter | F7 supply filter | Indoor humidity sensor | Electric heater for preheating | Hydraulic U-trap | Air damper | Electric actuator | Summer block |
VUT 160 V EC A11 | SF 285х195х10 G4 | SF 285х195х10 F7 | HV1 | NKP-125 | SH-32 | KRV 125 | LF230 | VL C6 366/285 |
VUE 160 V EC A11 | ||||||||
VUT 160 VB EC A11 | - | |||||||
VUE 160 VB EC A11 | ||||||||
VUT 160 V1 EC A11 | VL C6 366/285 | |||||||
VUE 160 V1 EC A11 | ||||||||
VUT 160 V1B EC A11 | - | |||||||
VUE 160 V1B EC A11 | ||||||||
VUT 250 V EC A11 | SF 417х200х18 G4 SF 384x196x40 G4 |
SF 417х184х18 F7 SF 384x196x40 F7 |
NKP-160 | KRV 160 | VL C6 366/384 | |||
VUT 250 VB EC A11 | - | |||||||
VUE 250 V EC A11 | VL C6 366/384 | |||||||
VUE 250 VB EC A11 | - | |||||||
VUT 350 V1B EC A11 | ||||||||
VUE 350 V1B EC A11 | ||||||||
VUT 350 VB EC A11 | SF 500х196х40 G4 | SF 500х196х40 F7 | ||||||
VUE 350 VB EC A11 | ||||||||
VUT 550 VB EC A11 | SF 630х198х40 G4 | SF 630х198х40 F7 | NKP-200 | KRV 200 | ||||
VUE 550 VB EC A11 |