VENTS VUT 1000 EH
Air handling unit with the air flow up to 1200 m³/h and heat recovery efficiency up to 78 % in sound-proof and heat-insulated casing with electric heater
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional characteristics
- Designation key
- Accessories
Description
Description
DESCRIPTION
|
AUTOMATION AND CONTROL SYSTEM
|
Characteristics
Characteristics
Parameter |
VUT 1000 EH |
Measurement unit |
---|---|---|
Frequency | 50 | Hz |
Phase | 3 | ˜ |
Voltage | 400 | V |
Electric heater power | 9000 | W |
Maximum fan power | 2 pcs. x 410 | W |
Electric heater current | 13 | A |
Air capacity | 1200 | m³/h |
Total unit current | 16.6 | A |
Fan current | 2 pcs. x 1.8 | A |
Total unit power | 9800 | W |
RPM | 1850 | min-1 |
Transported air temperature | -25...+40 | °С |
Sound pressure level at 3 m distance | 60 | dBА |
Casing material | aluzinc | - |
Heating | electric heating | - |
Insulation | 50 mm mineral wool | - |
Filter: extract | G4 | - |
Filter: supply | G4 | - |
Connected air duct size | 250 | mm |
Heat recovery efficiency | up to 78 | % |
Weight | 85 | kg |
Heat exchanger type | cross-flow | - |
Heat exchanger material | polystyrene | - |
Type | supply and exhaust with heat recovery | - |
Mounting | floor mounting | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 249 | mm |
B | 613 | mm |
B1 | 460 | mm |
B2 | 306 | mm |
B3 | 386 | mm |
H | 698 | mm |
H1 | 832 | mm |
H2 | 154 | mm |
H3 | 280 | mm |
L | 1071 | mm |
L1 | 1117 | mm |
L2 | 1171 | mm |
Additional characteristics
Additional characteristics
Sound-power level | Octave-frequency band [Hz] | |||||||||
Hz | Gen | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |
LwA to inlet | dBA | 69 | 68 | 66 | 68 | 68 | 60 | 63 | 61 | 54 |
LwA to outlet | dBA | 70 | 70 | 73 | 70 | 65 | 65 | 62 | 59 | 58 |
LwA to environment | dBA | 49 | 54 | 55 | 49 | 51 | 41 | 37 | 36 | 33 |
Designation key
Designation key
Series | Rated air flow [m³/h] | Heater type | Duct connection |
VENTS VUT | 350; 500; 530; 600; 800; 1000; 1500; 2000 | E: electric | H: horizontal |
Accessories
Accessories
Model | G4 panel filter | Silencers | Back valves | Air dampers | Clamps | Summer blocks | |
VUT 350 EH | SF 438x215x48 G4 | SR 125 600/900/1200 | SRF 125 600/900/1200 | KOM 125 | KR 125 | C 125 | VL C4 300/300 |
VUT 500 EH | SR 150 600/900/1200 | SRF 150 600/900/1200 | KOM 150 | KR 150 | C 150 | ||
VUT 530 EH | SR 160 600/900/1200 | SRF 160 600/900/1200 | KOM 160 | KR 160 | C 160 | ||
VUT 600 EH | SR 200 600/900/1200 | SRF 200 600/900/1200 | KOM 200 | KR 200 | C 200 | ||
VUT 800 EH | SF 550x253x48 G4 | SR 250 600/900/1200 | SRF 250 600/900/1200 | KOM 250 | KR 250 | C 250 | VL C4 300/300*2 |
VUT 1000 EH | |||||||
VUT 1500 EH | SF 780x273x48 G4 | SR 315 600/900/1200 | SRF 315 600/900/1200 | KOM 315 | KR 315 | C 315 | VL C4 300/384 |
VUT 2000 EH |