VENTS VUT 2000 H
Air handling unit with the air flow up to 2200 m³/h and the heat recovery efficiency up to 87 % in the compact sound- and heat-insulated casing
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional characteristics
- Designation key
- Accessories
Description
Description
DESCRIPTION
|
HEAT EXCHANGER
|
VUT H unit air exchange example in the flat |
Characteristics
Characteristics
Parameter |
VUT 2000 H |
Measurement unit |
---|---|---|
Frequency | 50/60 | Hz |
Phase | 1 | ˜ |
Voltage | 230 | V |
Maximum fan power | 2 pcs. x 650 | W |
Air capacity | 2200 | m³/h |
Total unit power | 1300 | W |
Fan current | 2 pcs. x 2.84 | A |
Total unit current | 5.68 | A |
RPM | 1150 | min-1 |
Transported air temperature | -25...+40 | °С |
Sound pressure level at 3 m distance | 65 | dBА |
Heating | without heating | - |
Casing material | aluzinc | - |
Insulation | 50 mm mineral wool | - |
Filter: extract | G4 | - |
Filter: supply | G4 | - |
Connected air duct size | 315 | mm |
Weight | 96 | kg |
Heat recovery efficiency | up to 87 | % |
Heat exchanger type | cross-flow | - |
Heat exchanger material | polystyrene | - |
Type | supply and exhaust with heat recovery | - |
Mounting | floor mounting, wall mounting, ceiling mounting | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
Ø D | 313 | mm |
B | 846 | mm |
B1 | 796 | mm |
B2 | 235 | mm |
B3 | 588 | mm |
H | 968 | mm |
H1 | 360 | mm |
H2 | 246 | mm |
L | 1000 | mm |
L1 | 1050 | mm |
Additional characteristics
Additional characteristics
Sound-power level | Octave-frequency band [Hz] | |||||||||
Hz | Gen | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |
LwA to inlet | dBA | 79 | 82 | 83 | 79 | 71 | 70 | 69 | 68 | 60 |
LwA to outlet | dBA | 81 | 82 | 82 | 77 | 72 | 79 | 73 | 74 | 67 |
LwA to environment | dBA | 55 | 65 | 66 | 60 | 52 | 49 | 46 | 40 | 38 |
Designation key
Designation key
Series | Rated air flow [m³/h] | Duct connection |
VENTS VUT | 350; 500; 530; 600; 1000; 2000 | H: horizontal |
Accessories
Accessories
Model | G4 panel filter | Silencers | Back valves | Air dampers | Clamps | Summer blocks | |
VUT 350 H | SF 378x210x48 G4 | SR 125 600/900/1200 | SRF 125 600/900/1200 | KOM 125 | KR 125 | C 125 | VL C4 200/384 |
VUT 500 H | SR 150 600/900/1200 | SRF 150 600/900/1200 | KOM 150 | KR 150 | C 150 | VL C4 300/384 | |
VUT 530 H | SR 160 600/900/1200 | SRF 160 600/900/1200 | KOM 160 | KR 160 | C 160 | ||
VUT 600 H | SR 200 600/900/1200 | SRF 200 600/900/1200 | KOM 200 | KR 200 | C 200 | ||
VUT 1000 H | SF 450х295х48 G4 | SR 250 600/900/1200 | SRF 250 600/900/1200 | KOM 250 | KR 250 | C 250 | VL C4 300/450 |
VUT 2000 H | SF 750х295х48 G4 | SR 315 600/900/1200 | SRF 315 600/900/1200 | KOM 315 | KR 315 | C 315 | VL C4 300/750 |