VENTS Non-insulated air ducts Thermovent Flex series

VENTS Non-insulated air ducts Thermovent Flex series

Semi-flexible stainless steel air ducts with high temperature resistance.

Model features
  • Ventilation ducts and fittings
  • Description
  • Downloads
Description
Description
DESCRIPTION FEATURES
  • Spiral seam stainless steel air ducts with high aerodynamic and strength characteristics.
  • Made of incombustible corrosion-resisting stainless steel band.
  • Increased thermal resistance (up to 800°С).
  • Specially designed high-quality locks ensure high seam tightness and total air tightness of the ducts.
  • Smooth internal surface ensures low dynamic losses.
  • Low weight and easy mounting.
RECOMMENDED APPLICATION
  • Applied in residential and industrial ventilation, air conditioning and heating systems with the maximum pressure 10 000 Pa.
  • For supply and exhaust ventilation.
  • Applied in the systems of hot air removal from boiler houses and smoke exhaust systems.
TECHNICAL DATA:  
   
Item Thermovent Flex
Diameter range [mm] 50/60/80/100/110/120/125/130/135/140/150/160/180/200/250/350/400
Material Stainless steel
Number of layers 2
Total thickness [μm] 100
Operating temperature range [°C] -30 +800
Maximum air speed [m/s] 30
Maximum operating pressure [Pa] 10000
Minimum bend radius [mm] up to Ø 200 mm 4D
above Ø 200 mm 4.5хD
Length [m] 1; 2; 3; 6
   
PRESSURE LOSS DIAGRAM PER 1 M STRETCHED AIR DUCT CALCULATION EXAMPLE:
 
  1. Select a curve that matches the air duct diameter [mm], 200 mm in this case.
  2. Find the intersection point of this line with the vertical line of the required air flow in m3/h, 500 m3/h in this case.
  3. The horizontal line that shows the pressure loss in Pa per 1 m straight air duct crosses this intersection point.
  4. Multiply pressure loss value (2.4 Pa/m at 20°С) by total air duct length to get the total pressure loss value. To calculate pressure loss in case of bends consider each bend as extra air duct meter.
Downloads
Downloads
Select document type
  • Advertising and printing products
  • Certificates
  • Technical documentation