VENTS Boost-I 200
Inline mixed-flow fans in sound- and heat-insulated casing. Air flow up to 1110 m³/h.
- Description
- Characteristics
- Downloads
- Dimensions
- Additional characteristics
- Designation key
Description
Description
APPLICATION | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
Characteristics
Characteristics
Parameter |
Boost-I 200 min |
Boost-I 200 mid |
Boost-I 200 max |
Measurement unit |
---|---|---|---|---|
Frequency | 50 | 50 | 50 | Hz |
Speed | min | mid | max | - |
Voltage | 230 | 230 | 230 | V |
Phase | 1 | 1 | 1 | ˜ |
Current | 0.37 | 0.46 | 0.51 | A |
Maximum air capacity | 192 | 252 | 308 | l/s |
Air capacity | 692 | 906 | 1110 | m³/h |
Power consumption | 82 | 104 | 113 | W |
Maximum air capacity | 692 | 906 | 1110 | m³/h |
EC motor | no | no | no | - |
RPM | 2229 | 2634 | 2823 | min-1 |
Sound pressure level at 3 m | 37 | 42 | 44 | dBА |
Protection rating | IP X4 | IP X4 | IP X4 | - |
Design | mixed-flow | mixed-flow | mixed-flow | - |
Motor protection rating | IP 20 | IP 20 | IP 20 | - |
Duct diameter | 200 | 200 | 200 | mm |
Transported air temperature | -25 ... +55 | -25 ... +55 | -25 ... +55 | °С |
Casing material | galvanized steel | galvanized steel | galvanized steel | - |
Weight | 8.2 | 8.2 | 8.2 | kg |
Outdoor mounting | no | no | no | - |
Sound-insulated casing | yes | yes | yes | - |
Duct | for round air ducts | for round air ducts | for round air ducts | - |
Type | supply and exhaust | supply and exhaust | supply and exhaust | - |
Mounting | Inline | Inline | Inline | - |
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 199 | mm |
∅D1 | 281 | mm |
B | 339 | mm |
L | 601 | mm |
L1 | 739 | mm |
Additional characteristics
Additional characteristics
Sound power level [A-filter] | Sound pressure level at a distance of 3 m [A-filter] | Sound pressure level at a distance of 1 m [A-filter] | ||||||||||
Sound power level | General | Octave frequency band [Hz] | ||||||||||
Hz | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | LpA, 3 m dBA | LpA, 1 m dBA | ||
LwA to inlet | dBA | 67 | 63 | 63 | 59 | 55 | 47 | 42 | 42 | 37 | 46 | 56 |
LwA to outlet | dBA | 68 | 65 | 64 | 59 | 57 | 49 | 45 | 45 | 36 | 48 | 58 |
LwA to environment | dBA | 64 | 55 | 51 | 61 | 60 | 40 | 40 | 28 | 22 | 44 | 54 |
Designation key
Designation key
Series | Air duct diameter | Options |
VENTS Boost-I | 200; 250 | Т: turn-off delay timer adjustable from 2 to 30 minutes. U: speed controller with an electronic thermostat and a temperature sensor integrated inside an air duct. Temperature-based operation logic. Un: speed controller with an electronic thermostat and a temperature sensor fixed on a 4-meter cable. Temperature-based operation logic. R: power cord with a mains plug. V: three-position speed switch. |
Accessories
Similar products