VENTS DVUT 500 HBE2 EC
Floor-mounted single-room air handling unit with air flow up to 580 m³/h in a heat and sound-insulated casing. Heat recovery efficiency up to 94 %.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional characteristics
- Designation key
- Accessories
Description
Description
Characteristics
Characteristics
Parameter |
DVUT 500 HBE2 EC |
Measurement unit |
---|---|---|
Frequency | 50/60 | Hz |
Phase | 1 | ˜ |
Voltage | 230 | V |
Max. unit current without electric heater | 1.7 | A |
Air capacity | 580 | m³/h |
Max. unit current with electric heater | 20 | A |
RPM | 1280 | min-1 |
Max. unit power without electric heater | 230 | W |
Reheater output | 2800 | W |
Preheater output | 1400 | W |
Heat recovery efficiency | 75...94 | % |
Transported air temperature | -25 ... +40 | °С |
Sound pressure level at 1 m distance | 35 | dBА |
Sound pressure level at 3 m distance | 25 | dBА |
Functions | Filter replacement indication, Timer, Weekly schedule, External sensor connection | - |
Heating | electric preheating, electric reheating | - |
Remote control panel | LCD, Sensor | - |
Casing material | painted steel | - |
Insulation | 40 mm mineral wool | - |
Filter: extract | G4x2 | - |
Filter: supply | G4, F8, * F8 + Carbon, * H11 | - |
Weight | 194 | kg |
Heat exchanger type | counter-flow | - |
Heat exchanger material | polystyrene | - |
SEC Class | A | - |
Duct | 250 | - |
Mounting | floor mounting | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
W | 750 | mm |
W1 | 290 | mm |
W2 | 230 | mm |
L | 535 | mm |
L1 | 585 | mm |
H1 | 1883 | mm |
H | 2170 | mm |
H2 | 337 | mm |
D | 250 | mm |
Additional characteristics
Additional characteristics
Fresh air stream length |
|
Designation key
Designation key
Unit series | Rated air flow [m³/h] | Installation | Bypass | Electric heaters | Drain pump | Motor type | Control |
DVUT – unit with plastic heat exchanger |
300; 500; 1200 |
H – floor-mounted with horizontal spigots | B – bypass damper | _ – no heater E – electric preheater E2 – electric preheater and reheater |
_ – without drain pump DN – in-built drain pump |
ЕС – synchronous motor with electronic control | А14 А21 |
Accessories
Accessories
Name | Image | DVUT 300 HB EC A14 | DVUT 300 HB EC A21 | DVUT 500 HB EC A14 | DVUT 500 HB EC A21 | DVUT 1200 HB EC A21 |
Outer ventilation hood made of white coated steel | NB DVUT 300 HB white | NB DVUT 500 HB white | NB DVUT 1200 HB white | |||
Outer ventilation hood made of brushed stainless steel | NB DVUT 300 HB chrome | NB DVUT 500 HB chrome | NB DVUT 1200 HB chrome | |||
Outer ventilation grille made of aluminium | MVMA 200 bVn Al | MVMA 250 bVn Al | MVMA 400 bVn Al | |||
G4 panel filter | SF 308x238x22 G4 PPI | SF 450x257x27 G4 PPI | SF 450x395x48 G4 PET | |||
G4 panel filter | SF 265x213x48 G4 | SF 318x290x22 G4 | SF 540x450x48 G4 | |||
F7 panel filter | – | – | SF 540x450x48 F7 | |||
F8 panel filter | SF 384x273x60 F8 | SF 318x290x60 F8 | – | |||
F8 panel carbon filter | SF 533x135x48 F8 C | SF 666x196x48 F8 C | – | |||
HEPA panel filter | SF 533x135x60 H11 | SF 666x196x60 H11 | – | |||
VOC sensor (0-10 V) | – | DPWQ30600 | – | DPWQ30600 | DPWQ30600 | |
СО2 sensor (0-10 V) | – | DPWQ40200 | – | DPWQ40200 | DPWQ40200 | |
Humidity sensor (0-10 V) | – | DPWС11200 | – | DPWС11200 | DPWС11200 | |
Humidity sensor (NO) | HR-S | |||||
Humidity sensor | HV2 | |||||
Hydraulic U-trap | SG-32 | |||||
Drain pump | DN-2 |