Login

Privacy Policy (GDPR)
Authorization
Not registered yet? Take advantages of registration:
Products saving in a binding to the projects
Product consultation from our experts - Online
Registration
Signup
By using this form, you confirm that you have read the site terms of use Terms of use and completely accept the terms of use

VENTS NK 160-1,2-1 U

  • Description
  • Characteristics
  • Downloads
  • Dimensions
  • Legend
Description
Description
APPLICATIONS

Duct electrical heaters are designed for supply air heating in round duct ventilating system. The heaters are applied in heating, ventilation and air conditioning systems for various premises.

DESIGN

The casing and the terminal box are made of galvanized steel and the heating elements are of stainless steel. The heaters are equipped with rubber seals for connection to the air ducts.

NK duct heaters are equipped with two overheating protection thermostats:

  • basic protection with automatic restart with +50 °С operating temperature. After cooling the thermostat closes the control circuit of the heater automatically.
  • emergency protection with manual restart (operating temperature +90 °С). In case of response the power supply to the heater is allowed after the manual emergency reset only.
  • the thermostat contacts are located in the terminal box for external connection.

Each standard size has several electric capacity options. The higher capacity can be attained by means of installation of the heaters in series. All the three phase heaters have star connection.

DUCT ELECTRIC HEATER WITH INTEGRATED TEMPERATURE CONTROL

The NK heaters are available in modifications NK...U with a temperature controller for the heaters with power demand from 0.6 up to 2.4 kW or with a control unit for the heaters with power demand from 3.0 up to 9.0 kW to maintain set air temperature in the air duct.

  • NK…U duct heater with a temperature controller, power demand from 0.6 up to 2.4 kW

The temperature control knob with temperature range from -10 °C up to +40 °C is placed on the junction box front panel. The NK…U heater is equipped with a builtin temperature sensor located inside of the air duct.

The thermal switch with manual reset actuated at +60 °C is used for the thermal overheat protection.

  • NK…U duct heater with a control unit, power demand from 3.0 up to 9.0 kW

The NK…U model with a control unit is equipped with a triac power control unit. Power control is effected by means of switching on/off the maximum load commutated by the semiconductor device that is free of any mechanical wear parts. The load commutation starts at zero current and load to disable any magnetic field interferences.

The NK…U heater includes two overheat protection thermostats:

  • the basic self-resetting overheat protection thermostat actuated at the temperature +50 °C.

After cooling the thermostat closes the heater control circuit.

  • the emergency overheat protection thermostat with manual reset actuated at the temperature +90 °C. In case of the thermostat tripping power supply is resumed after manual alarm reset.

Operation logic options for the NK…U heater with a control unit:

  • operation logic based on temperature sensor readings to maintain set air temperature in the air duct.
  • proportional electric heat control from 0 up to 100% with a 0-10 V control signal from the external controller.

The temperature is set with the integrated potentiometer. Optionally, an external 0-10 V control signal from another control unit may be connected to the control unit, which corresponds to the temperature 0 up to +40 °C.

Offered temperature sensor options for the NK...U heater operation logic based on temperature sensor readings (not included into delivery set):

  • KDT2-M1 duct temperature sensor enclosed in a protecting sleeve with a sensing tip, 100 up to 400 mm long.
  • KDT2-M duct temperature sensor enclosed in a protecting sleeve with a mounting flange, 100 up to 400 mm long.
  • KDT2-MK duct temperature sensor enclosed in a protecting sleeve with a mounting flange, 100 up to 400 mm long.
MOUNTING

The heater design ensures its mounting on the round ducts in any position by means of clamps. The air flow direction shall match the pointer on the filter. The duct heaters can be installed in any position except for with the electric control unit below to prevent liquid penetration and wiring short circuit.

The mounting shall be performed in such a way as to enable uniform air distribution along the entire cross section.

The air filter shall be installed at heater inlet to protect the heating elements against pollution.

The minimum distance between the heater and other system elements is no less than two connecting diameters.

The duct heaters are designed for minimum air flow speed 1.5 m/s and the maximum operating outlet temperature 40 °С. In case of speed control option ensure the minimum air flow through the heater.

Power supply to the heater shall be disabled if the fan is not running.

To ensure the correct and safe heater operation he automation system can be applied to ensure the complex control and protection:

  • automatic control of heating elements capacity and air heating temperature;
  • checkingfilter condition by means of differential pressure sensor;
  • power supply disabling in case of supply fan shutdown or airflow speed decrease as well as in case of the built-in overheating thermostats operation;
  • shutoff of ventilating system with blowing of electrical heating elements.

 

Characteristics
Characteristics
Parameter NK 160-1,2-1 U
Measurement unit
Minimum air capacity 150 m³/h
Current 5.2 A
Voltage Voltage 230 V
Power 1.2 W
Number of heating coils x capacity Number of heating coils x capacity 1 х 1,2 kW
Weight 2.2 kg
Air duct diameter Air duct diameter 160 mm
Phase Phase 1 ˜
Heating electric heating -
Duct for round air ducts -
Connection diameter 160 mm
Files archieve
Downloads
Select document type
  • Advertising and printing products
  • Certificates
  • Technical documentation
Name
"NK, NK...U (round)" product description 02-2016 (pdf 351.54Kb)
Download high quality image "NK...U with temperature controller (round)" (psd 2.22Mb)
Download image "NK...U with temperature controller (round)" for your website (png 699.89Kb)
"NK...U" user's manual 12-2020 (V09-2EN-06) (pdf 3.69Mb)
Download high quality image "NK...U with control unit (round)" (psd 1.88Mb)
Download image "NK...U with control unit (round)" for your website (png 570.38Kb)
Dimensions
Characteristics
VENTS NK 160-1,2-1 U
Parameter Value Measurement unit
∅D 159 mm
B 154 mm
H 267 mm
L 306 mm
L1 226 mm
Legend
Legend
Series   Air duct diameter, mm   Heater power [kW]   Phase   Options
NK   100; 125; 150; 160; 200; 250; 315   0,6; 0,8; 1,2; 1,6; 1,7; 2,0; 1,8; 2,4; 3,0; 3,4; 3,6; 5,1; 6,0; 9,0   1-single phase
3
-three phase
  U – integrated temperature control
Share your opinion

Questionnaire
Please evaluate our updated site user friendliness