VENTS PA 03 E
Suspended air supply unit with the air flow up to 3350 m³/h in the sound- and heat-insulated casing with the electric heater
- Description
- Characteristics
- Downloads
- Dimensions
- Additional characteristics
- Designation key
- Accessories
Description
Description
DESCRIPTION | CASING |
|
|
FILTER | HEATER |
|
|
FAN | |
|
|
MOUNTING | |
|
|
CONTROL AND AUTOMATION | |
|
|
CONTROL AND PROTECTION FUNCTIONS | |
|
|
Characteristics
Characteristics
Parameter |
PA 03 E |
Measurement unit |
---|---|---|
Frequency | 50 | Hz |
Phase | 3 | ˜ |
Voltage | 400 | V |
Maximum fan power | 1330 | W |
Fan current | 2.4 | A |
Electric heater power | 21000 | W |
Electric heater current | 30 | A |
Air capacity | 3350 | m³/h |
Total unit power | 22330 | W |
Total unit current | 32.4 | A |
RPM | 2730 | min-1 |
Filter | panel filter G4 | - |
Transported air temperature | -25 ... +40 | °С |
Sound pressure level at 3 m distance | 57 | dBА |
Casing material | aluzinc | - |
Heating | electric heating | - |
Insulation | 50 mm mineral wool | - |
Connected air duct size | 600х350 | mm |
Width | 600 | mm |
Weight | 91 | kg |
Height | 350 | mm |
Duct | for rectangular air ducts | - |
Files archieve
Downloads
Select document type
"Control system for air supply and air handling units based on Freemax controllers and AC208A2 sensor control panels" user's manual 07-2023 (V99EN-03) (pdf 7.14Mb)
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
B | 600 | mm |
B1 | 620 | mm |
B2 | 888 | mm |
B3 | 744 | mm |
H | 350 | mm |
H1 | 370 | mm |
H2 | 500 | mm |
L | 1252 | mm |
L1 | 1212 | mm |
Additional characteristics
Additional characteristics
Sound-power level | Gen | Octave-frequency band [Hz] | ||||||||
63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||
LWA to inlet | dBA | 72 | 58 | 71 | 67 | 59 | 49 | 51 | 56 | 54 |
LWA to outlet | dBA | 77 | 58 | 71 | 73 | 71 | 70 | 68 | 65 | 55 |
LWA to environment | dBA | 58 | 41 | 59 | 62 | 51 | 47 | 53 | 51 | 46 |
Designation key
Designation key
Series | Unit standard size | Heater type | Integrated control system |
VENTS PA | 01; 02; 03; 04 | Е: electric | LCD: integrated automation with A16 control panel |
Accessories
Accessories
Type | G4 replaceable filter | Filter type |
PА 01 Е | SF 475x270x48 G4 | panel filter |
PА 02 Е | SF 540x340x48 G4 | panel filter |
PА 03 Е | SF 635x395x48 G4 | panel filter |
Accessories