VENTS PA…E series supply units
- Description
- Modifications
- Downloads
- Designation key
- Accessories
Description
Description
DESCRIPTION |
CASING |
- The PA unit is a ready to use ventilation unit for air filtration, warming and supply to the room.
|
- Steel casing covered with aluzinc coating internally filled with 50 mm heat- and sound-insulating layer made of mineral wool.
|
FILTER |
HEATER |
- Integrated panel G4 filter ensures sufficient supply air purification (optionally F7).
|
- The PA units are equipped with electric heater.
|
FAN |
|
- The unit is equipped with a direct-driven centrifugal fan with backward curved blades and external rotor motor.
|
- The fan configuration ensures the best operating characteristics: high air flow and efficiency combined with low noise level.
|
MOUNTING |
|
- The unit is designed for indoor installation either on the floor, on the wall or under the ceiling by means of a seat angle with inserted vibration-damping element or attached to a wall with brackets.
- The unit can be mounted either in service spaces or in main premises above the suspended ceiling, in the pocket or the unit can be placed directly in the room.
- All the electrical connections are performed through the terminal box placed in the connection box.
|
- PA supply units are supplied with the fastening brackets to facilitate mounting.
- The unit can be mounted in any position but the vertical one with vertical air downstream because the electrical heating elements are not allowed under the fan.
- Access for the unit maintenance and filter cleaning shall be provided.
|
CONTROL AND AUTOMATION |
|
- Integrated control and automation system for speed (air flow) control and setting supply air temperature.
|
- The unit may be remotely controlled from the external control panel fixed on wire.
|
CONTROL AND PROTECTION FUNCTIONS |
|
- control from the control panel: switching the unit on/off, fan speed selection (low/medium/high speed), selecting heating/cooling modes (if connected to duct heater);
- maintaining supply air temperature set from the control panel by smooth heating capacity control;
- smooth frequency speed control of the fan;
- safe start-up/shutdown of the fans;
- Active overheating protection of the electric heating elements by the temperature sensor and by the thermostats activated at 60 °C with automatic reset and at 90 °C with manual reset. Blowing of the electric heating elements for heat removal at the end of the heating cycle.
|
- Filter clogging control with differential pressure sensor.
- Actuating the external air damper.
- Input from the fire alarm system.
- Control of the compressor and condensing block of the water cooler by the room temperature sensor (for models with external duct air cooler).
- Maintaining of set supply air temperature set from the control panel by smooth heating capacity control;
- smooth frequency fan speed control.
|
Designation key
Designation key
Series |
Unit standard size |
Heater type |
Integrated control system |
VENTS PA |
01; 02; 03; 04 |
Е: electric |
LCD: integrated automation with A16 control panel |
Accessories
Accessories
Type |
G4 replaceable filter |
Filter type |
PА 01 Е |
SF 475x270x48 G4 |
panel filter |
PА 02 Е |
SF 540x340x48 G4 |
panel filter |
PА 03 Е |
SF 635x395x48 G4 |
panel filter |