Characteristics
Characteristics
Parameter |
VKM 100 Q 50 Hz |
VKM 100 Q 60 Hz |
Measurement unit |
---|---|---|---|
Phase | 1 | 1 | ˜ |
Voltage | 220-240 | 220-240 | V |
Frequency | 50 | 60 | Hz |
Sound pressure level at 3 m distance | 38 | 39 | dBА |
Power consumption | 45 | 50 | W |
Maximum air capacity | 233 | 267 | m³/h |
Current | 0.24 | 0.23 | A |
Max. transported air temperature | -25 +45 | -25 +45 | °С |
RPM | 2780 | 3300 | min-1 |
Protection rating | IP X4 | IP X4 | - |
Design | centrifugal | centrifugal | - |
Duct diameter | 100 | 100 | mm |
Weight | 2.1 | 2.1 | kg |
Casing material | polymer coated steel | polymer coated steel | - |
SEC Class | C | - | - |
Duct | for round air ducts | for round air ducts | - |
Type | supply and exhaust | supply and exhaust | - |
Mounting | Inline | Inline | - |
* | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 98 | mm |
B1 | 270 | mm |
ØD1 | 255 | mm |
B | 310 | mm |
L | 205 | mm |
L1 | 20 | mm |
L2 | 25 | mm |
L3 | 30 | mm |
Additional diagrams
Additional diagrams
Sound-power level | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||||
Gen. | Octave-frequency band [Hz] | |||||||||||
Hz | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to inlet | dBA | 78 | 56 | 70 | 77 | 68 | 63 | 59 | 53 | 43 | 58 | 68 |
LwA to outlet | dBA | 77 | 63 | 70 | 75 | 67 | 60 | 56 | 52 | 41 | 57 | 67 |
LwA to environment | dBA | 59 | 27 | 47 | 49 | 53 | 54 | 51 | 42 | 32 | 38 | 48 |
Designation key
Designation key
Series | Air duct diameter | Options | |
VENTS VKМ | S: high- powered motor |
100; 125; 150; 160; 200; 250; 315; 355; 400; 450 |
Е: low energy demand motor. Q: low-powered motor. Un: speed controller with an electronic thermostat and a temperature sensor fixed on a 4 m cable. Temperature-based operation logic. U2n: speed controller with an electronic thermostat and a temperature sensor fixed on a 4-meter cable. Temperature-based switching on/off. R1: power cord with a mains plug. P: integrated smooth speed controller. |
Accessories