VENTS VKM 160
Inline centrifugal fans in steel casing with air flow up to 575 m³/h.
3D model
Gallery
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional diagrams
- Designation key
Description
Description
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
THE FAN WITH ELECTRONIC TEMPERATURE AND CONTROL MODULE (U OPTION) | |
|
|
VENTS VKM fan catering ventilation example |
Characteristics
Characteristics
Parameter |
VKM 160 50 Hz |
VKM 160 60 Hz |
Measurement unit |
---|---|---|---|
Phase | 1 | 1 | ˜ |
Voltage | 220-240 | 220-240 | V |
Frequency | 50 | 60 | Hz |
Sound pressure level at 3 m distance | 45 | 47 | dBА |
Power consumption | 99 | 137 | W |
Maximum air capacity | 567 | 575 | m³/h |
Current | 0.44 | 0.61 | A |
Max. transported air temperature | -25 +45 | -25 +45 | °С |
RPM | 2770 | 3160 | min-1 |
Protection rating | IP X4 | IP X4 | - |
Design | centrifugal | centrifugal | - |
Duct diameter | 160 | 160 | mm |
Weight | 5.0 | 5.0 | kg |
Casing material | polymer coated steel | polymer coated steel | - |
SEC Class | C | - | - |
Duct | for round air ducts | for round air ducts | - |
Type | supply and exhaust | supply and exhaust | - |
Mounting | Inline | Inline | - |
* | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 159 | mm |
B1 | 320 | mm |
ØD1 | 305 | mm |
B | 360 | mm |
L | 220 | mm |
L1 | 25 | mm |
L2 | 25 | mm |
L3 | 30 | mm |
Additional diagrams
Additional diagrams
Sound-power level | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||||
Gen. | Octave-frequency band [Hz] | |||||||||||
Hz | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to inlet | dBA | 88 | 52 | 85 | 84 | 74 | 73 | 70 | 67 | 53 | 68 | 78 |
LwA to outlet | dBA | 87 | 51 | 85 | 82 | 70 | 69 | 64 | 63 | 50 | 67 | 77 |
LwA to environment | dBA | 65 | 28 | 48 | 58 | 58 | 60 | 59 | 51 | 38 | 45 | 55 |
Designation key
Designation key
Series | Air duct diameter | Options | |
VENTS VKМ | S: high- powered motor |
100; 125; 150; 160; 200; 250; 315; 355; 400; 450 |
Е: low energy demand motor. Q: low-powered motor. Un: speed controller with an electronic thermostat and a temperature sensor fixed on a 4 m cable. Temperature-based operation logic. U2n: speed controller with an electronic thermostat and a temperature sensor fixed on a 4-meter cable. Temperature-based switching on/off. R1: power cord with a mains plug. P: integrated smooth speed controller. |
Accessories