VENTS VKMSz 200
Inline centrifugal fan. Maximum capacity - 1140 m3/h.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional technical data
- Designation key
Description
Description
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
Characteristics
Characteristics
Parameter |
VKMSz 200 50 Hz |
VKMSz 200 60 Hz |
Measurement unit |
---|---|---|---|
Low-powered motor | no | no | - |
Voltage | 1~ 220-240 | 1~ 220-240 | V |
Frequency | 50 | 60 | Hz |
Sound pressure level at 3 m distance | 50 | 50 | dBА |
Power consumption | 186 | 240 | W |
Current | 0.81 | 1.05 | A |
Maximum air capacity | 1110 | 1140 | m³/h |
RPM | 2810 | 3222 | min-1 |
Max. transported air temperature | -25 +50 | -25 +50 | °С |
Protection rating | IP X4 | IP X4 | - |
Design | centrifugal | centrifugal | - |
Motor protection rating | IP44 | IP44 | - |
Weight | 5.8 | 5.8 | kg |
Duct diameter | 200 | 200 | mm |
Casing material | galvanized steel | galvanized steel | - |
Outdoor mounting | yes | yes | - |
SEC Class | B | B | - |
Duct | for round air ducts | for round air ducts | - |
Mounting | outdoor mounting, wall mounting, Inline | outdoor mounting, wall mounting, Inline | - |
* | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 198 | mm |
B1 | 395 | mm |
ØD1 | 339 | mm |
B | 355 | mm |
L | 245 | mm |
L1 | 25 | mm |
L2 | 29 | mm |
L3 | 40 | mm |
Additional technical data
Additional technical data
Sound-power level | ||||||||||
Gen. | Octave-frequency band [Hz] | |||||||||
Hz | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||
LwA to inlet | dBA | 76 | 47 | 68 | 65 | 70 | 67 | 59 | 58 | 50 |
LwA to outlet | dBA | 76 | 49 | 71 | 69 | 72 | 63 | 63 | 60 | 53 |
LwA to environment | dBA | 64 | 46 | 61 | 57 | 48 | 32 | 27 | 48 | 42 |
Designation key
Designation key
Series | Air duct diameter | Options | |
VENTS VKMz | S: high-powered motor |
100; 125; 150; 160; 200; 250; 315 |
Q: low-powered motor R1: power cord with a mains plug |
Accessories