VENTS VKP 800x500 L3 EC
Centrifugal fans with the air capacity up to 8535 m³/h for rectangular ducts.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional diagrams
- Designation key
Description
Description
APPLICATIONS | INTEGRATED FUNCTIONS AND CONTROL |
|
|
DESIGN | MOTOR |
|
|
VENTS VKP EC fan school class ventilation example | VENTS VKP EC fan car parking stand ventilation example |
Characteristics
Characteristics
Parameter |
VKP 800x500 L3 EC |
Measurement unit |
---|---|---|
SEC class* | - | - |
Phase | 3 | ˜ |
Voltage | 400 | V |
Frequency | 50/60 | Hz |
Current | 3.05 | A |
Power consumption | 2925 | W |
Maximum air capacity | 8535 | m³/h |
RPM | 2400 | min-1 |
EC motor | yes | - |
Max. transported air temperature | -25 +50 | °С |
Protection rating | IP X4 | - |
Design | centrifugal | - |
Weight | 54.3 | kg |
Sound pressure level at 3 m distance | 63 | dBА |
Casing material | galvanized steel | - |
Duct | for rectangular air ducts | - |
Type | supply and exhaust | - |
Mounting | Inline | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
В | 800 | mm |
B1 | 820 | mm |
B2 | 840 | mm |
H | 500 | mm |
H1 | 520 | mm |
H2 | 540 | mm |
H3 | 670 | mm |
L | 850 | mm |
Additional diagrams
Additional diagrams
Sound power level, A-filter applied | Sound pressure level at 3 meters, A-filter applied | Sound pressure level at 1 meter, A-filter applied | ||||||||||
Sound-power level, A - weighted | General | Octave frequency band [Hz] | ||||||||||
Hz | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | LpA, 3 m [dBA] | LpA, 1 m [dBA] | ||
LwA to inlet | dBA | 90 | 59 | 83 | 81 | 85 | 83 | 80 | 76 | 77 | 70 | 80 |
LwA to outlet | dBA | 93 | 57 | 84 | 87 | 87 | 88 | 83 | 76 | 76 | 73 | 83 |
LwA to environment | dBA | 83 | 59 | 81 | 77 | 72 | 70 | 65 | 59 | 56 | 63 | 73 |
Designation key
Designation key
Series | Flange diameter [WxH] | Motor modification | Phase | Motor |
VENTS VKP | 300х150, 400х200, 500х250, 500х300, 600х300, 600х350, 700х400, 800х500, 900х500, 1000х500 |
M: medium pressure motor |
1: single phase 3: three phase |
ЕС - synchronous electronically commutated motor |
Accessories
Similar products