DESCRIPTION | |
|
|
MODIFICATIONS | CASING |
|
|
FILTER | |
|
|
MOTOR | |
|
|
HEAT EXCHANGER | |
|
|
HEATER | CONTROL AND AUTOMATION |
|
|
The VUT PE EC unit incorporates a LCD control panel with a colour sensor display PU SENS 01. |
|
VUT PE EC CONTROL AND PROTECTION FUNCTIONS | |
Control panel:
|
|
MOUNTING
|
|
|
|
ACCESSORIES | |
|
|
Parameter |
VUT 1000 PE EC |
Measurement unit |
---|---|---|
Frequency | 50/60 | Hz |
Phase | 1 | ˜ |
Voltage | 230 | V |
Maximum fan power | 400 | W |
Fan current | 2,26 | A |
Electric heater power | 3,3 | W |
Electric heater current | 14.3 | A |
Total unit power | 3700 | W |
Total unit current | 16.56 | A |
Maximum air capacity | 1100 | m³/h |
RPM | 2780 | min-1 |
Sound pressure level at 3 m distance | 52 | dBА |
Transported air temperature | -25 up to +40 | °С |
Casing material | aluzinc | - |
Insulation | 20 mm mineral wool | - |
Filter: extract | G4 | - |
Filter: supply | G4 (F7*) | - |
Connected air duct size | 250 | mm |
Number of water (glycol) coil rows | - | - |
Weight | 95 | kg |
Heat recovery efficiency | up to 90 | % |
Heat exchanger type | counter-flow | - |
Heat exchanger material | aluminium | - |
SEC Class | - | - |
Parameter | Value | Measurement unit |
---|---|---|
∅D | 250 | mm |
B | 1351 | mm |
B1 | 1216 | mm |
B2 | 608 | mm |
B3 | 431 | mm |
B4 | 655 | mm |
H | 318 | mm |
H1 | 143 | mm |
L | 1349 | mm |
L1 | 1402 | mm |
L2 | - | mm |
Sound-power level | Octave-frequency band [Hz] | |||||||||
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |
LWA to inlet | dBA | 68 | 67 | 68 | 70 | 68 | 60 | 60 | 61 | 55 |
LWA to outlet | dBA | 70 | 71 | 69 | 68 | 66 | 65 | 63 | 61 | 58 |
LWA to environment | dBA | 45 | 57 | 56 | 47 | 52 | 42 | 38 | 34 | 35 |
Model | G4 pocket filter | F7 pocket filter | G4 panel filter | Outdoor humidity sensor | Silencer | Backdraft damper | Air damper | Clamps | Electric actuators | Mixing unit | ||
VUT 350 PE ЕC | SFK 208х236х27 G4 | SFK 208х236х27 F7 | SF 440х128х20 G4 | HV1 | SR 160 600/900/1200 | SRF 160 600/900/1200 | KOM 160 | KRV | С 160 | LF 230 | TF 230 | - |
VUT 600 PE ЕC | SFK 392х236х27 G4 | SFK 392х236х27 F7 | >SF 782х128х20 G4 | SR 200 600/900/1200 | SRF 200 600/900/1200 | КОМ 200 | KRV 200 | С 200 | LF 230 | TF 230 | - | |
VUT 1000 PE ЕC | SFK 647х274х27 G4 | SFK 647х274х27 F7 | SF 647х274х20 G4 | SR 250 600/900/1200 | SRF 250 600/900/1200 | КОМ 250 | KRV 250 | С 250 | LF 230 | TF 230 | - | |
VUT 2000 PE ЕC | - | - | SF 708х480х48 G4 | SR 315 600/900/1200 | SRF 315 600/900/1200 | КОМ 315 | KRV 315 | С 315 | LF 230 | TF 230 | - | |
VUT 3000 PE ЕC | - | - | SF 827х741х48 G4 | SR 400 600/900/1200 | SRF 400 600/900/1200 | КОМ 400 | KRV 400 | С 400 | LF 230 | TF 230 | - |
Series | Rated air flow, [m3/h] | Mounting modification | Heater type | Motor type | Service side | Control |
VENTS VUT | 350; 600; 1000; 2000; 3000 | P: suspended | E: electric | ЕС:synchronous electronically commutated motor |
L: left
R: right
|
_ : PU SENS 01 control panel |