VENTS TT Silent-M 315
Inline mixed-flow fans in sound- and heat-insulated casing with the air flow up to 2050 m³/h.
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional diagrams
- BIM
- Designation key
Description
Description
APPLICATION | |
|
|
DESIGN | |
|
|
|
|
MOTOR | |
|
|
CONTROL | |
|
|
TT Silent-M fan with a three-position speed switch | |
|
|
TT Silent-M fan with a built-in speed controller | |
MOUNTING | |
|
|
THE FAN WITH ELECTRONIC MODULE OF THE TEMPERATURE SENSOR AND SPEED CONTROLLER («U» OPTION) | |
|
|
The front panel of the electronic module has the following control knobs: | |
|
|
The fan is available in two modifications: | |
|
|
CONTROL LOGIC OF THE FAN WITH THE ELECTRONIC TEMPERATURE AND SPEED CONTROL MODULE | |
|
|
There are two switch delay control logics for various cases: | |
|
|
Characteristics
Characteristics
Parameter |
TT Silent-M 315 min |
TT Silent-M 315 max |
Measurement unit |
---|---|---|---|
Speed | min | max | - |
Phase | 1 | 1 | ˜ |
Voltage | 230 | 230 | V |
Frequency | 50/60 | 50/60 | Hz |
Fan power | 230 | 330 | W |
RPM | 1890 | 2430 | min-1 |
Current | 1.0 | 1.42 | A |
Maximum air capacity | 1570 | 2050 | m³/h |
Max. transported air temperature | 60 | 60 | °С |
Sound pressure level at 3 m | 36 | 40 | dBА |
Protection rating | IP X4 | IP X4 | - |
Duct diameter | 315 | 315 | mm |
Sound- and heat-insulated casing | yes | yes | - |
Casing material | polymer coated steel | polymer coated steel | - |
Weight | 25 | 25 | kg |
SEC Class | - | - | - |
Duct | for round air ducts | for round air ducts | - |
Type | supply and exhaust | supply and exhaust | - |
Mounting | floor mounting, wall mounting, ceiling mounting, Inline | floor mounting, wall mounting, ceiling mounting, Inline | - |
* | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | To meet the requirements of ErP 2018, a speed controller and local demand control typology must be applied (connect a sensor). | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
"TT-M, TT-MD, TT-MD EC, TT Silent-M, TT Silent-MD, TT Silent-MD EC" user's manual 06-2018 (V135EN-03) (pdf 3.41Mb)
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 313 | mm |
B | 432 | mm |
B1 | 520 | mm |
H | 434 | mm |
L | 780 | mm |
Additional diagrams
Additional diagrams
Low speed | Gen. | Octave-frequency band [Hz] | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||
Sound-power level | dBA | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||
LwA to inlet | dBA | 67 | 36 | 57 | 63 | 61 | 59 | 43 | 32 | 18 | 46 | 56 |
LwA to outlet | dBA | 65 | 45 | 48 | 56 | 59 | 61 | 56 | 48 | 37 | 44 | 54 |
LwA to environment | dBA | 56 | 47 | 47 | 52 | 50 | 45 | 41 | 37 | 29 | 36 | 46 |
High speed | Gen. | Octave-frequency band [Hz] | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||
Sound-power level | dBA | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||
LwA to inlet | dBA | 70 | 38 | 60 | 67 | 64 | 62 | 45 | 34 | 18 | 49 | 59 |
LwA to outlet | dBA | 71 | 50 | 53 | 62 | 65 | 67 | 62 | 53 | 41 | 50 | 60 |
LwA to environment | dBA | 60 | 51 | 52 | 54 | 55 | 50 | 46 | 43 | 35 | 40 | 50 |
ƞ, [%] | MC | EC | N | VSD | kW | A | m3/h | Pa | RPM | SR |
32.4 | А | static | 48.2 | No | 0.317 | 1.43 | 1112 | 326 | 2320 | 1 |
Designation key
Designation key
|
|
Accessories
Similar products