VENTS VUT 550 PBW EC
- Description
- Characteristics
- Capacity diagram
- Downloads
- Dimensions
- Additional characteristics
- Designation key
- Accessories
Description
Description
DESCRIPTION
|
MODIFICATIONS
|
Characteristics
Characteristics
Parameter |
VUT 550 PBW EC |
Measurement unit |
---|---|---|
Frequency | 50/60 | Hz |
Phase | 1 | ˜ |
Voltage | 230 | V |
Maximum unit power | 297 | W |
Maximum unit current | 2.4 | A |
Air capacity | 620 | m³/h |
Number of water (glycol) coil rows | 2 | - |
RPM | 3100 | min-1 |
Transported air temperature | -25 ... +40 | °С |
Sound pressure level at 3 m distance | 30 | dBА |
Heating | water heating | - |
Casing material | aluzinc | - |
Insulation | 20 mm mineral wool | - |
Filter: extract | G4 | - |
Filter: supply | G4 (F7*) | - |
Connected air duct size | 200 | mm |
Heat recovery efficiency | 78-90 | % |
Weight | 68 | kg |
Heat exchanger type | counter-flow | - |
Heat exchanger material | polystyrene | - |
SEC Class | A | - |
Capacity diagram
Capacity diagram
- Selection method:
- Air flow:
- Pressure:
Operating point
- Air flow: --
- Pressure: ---
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 200 | mm |
B | 827 | mm |
B1 | 960 | mm |
H | 280 | mm |
L | 1238 | mm |
L1 | 1291 | mm |
Additional characteristics
Additional characteristics
A-weighted sound power level | Gen. | Octave frequency band, Hz | LpA, 3 m dBA | LpA, 1 m dBA | ||||||||
dBA | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | ||||
LwA to supply inlet | dBA | 69 | 26 | 60 | 68 | 54 | 53 | 48 | 40 | 29 | ||
LwA to supply outlet | dBA | 76 | 27 | 62 | 71 | 66 | 68 | 68 | 66 | 64 | ||
LwA to exhaust inlet | dBA | 66 | 24 | 55 | 65 | 53 | 53 | 49 | 41 | 35 | ||
LwA to exhaust outlet | dBA | 69 | 26 | 60 | 68 | 54 | 53 | 48 | 40 | 29 | ||
LwA to environment | dBA | 50 | 29 | 40 | 46 | 46 | 38 | 36 | 34 | 36 | 30 | 40 |
WATER HEATER PARAMETERS CALCULATION
|
Designation key
Designation key
Series | Rated air flow [m³/h] | Mounting modification | Bypass | Heater type | Motor type | Service side | Control | Accessories |
VUT: ventilation with heat recovery VUE: ventilation with energy recovery |
300; 550; 900; 2000; 3000 | P: suspended | B: bypass | E: electric W: water |
EC: synchronous electronically commutated motor | L: left R: right |
А21 | DTV: equipped with a differential pressure switch for controlling the contamination of filters |
Accessories
Accessories
Model | G4 pocket filter | F7 pocket filter | G4 panel filter | Control panel | Wi-Fi controlable control panel | LCD control panel | Humidity sensor (0-10 V) |
CO2 sensor | CO2 sensor with indication | Humidity sensor | VOC sensor (0-10 V) |
CO2 sensor (0-10 V) |
Humidity sensor (0-10 V) |
VUT 300 PBE EC A21 | SFK 208x236x27 G4 | SFK 208x236x27 F7 | SF 440x128x20 G4 | A22 | A22 WiFi | A25 | HV2 | CO2-1 | CO2-2 | HR-S | DPWQ 30600 | DPWQ 40200 | DPWC 11200 |
VUT 550 PBE EC A21 | SFK 392x236x27 G4 | SFK 392x236x27 F7 | SF 782x128x20 G4 | ||||||||||
VUT 900 PBE EC A21 | SFK 647x274x27 G4 | SFK 647x274x27 F7 | SF 647x274x20 G4 | ||||||||||
VUE 300 PBE EC A21 | SFK 208x236x27 G4 | SFK 208x236x27 F7 | SF 440x128x20 G4 | ||||||||||
VUE 550 PBE EC A21 | SFK 392x236x27 G4 | SFK 392x236x27 F7 | SF 782x128x20 G4 | ||||||||||
VUE 900 PBE EC A21 | SFK 647x274x27 G4 | SFK 647x274x27 F7 | SF 647x274x20 G4 | ||||||||||
VUT 2000 PBE EC A21 | – | – | SF 708x480x48 G4 | ||||||||||
VUT 3000 PBE EC A21 | – | – | SF 827x741x48 G4 | ||||||||||
VUT 550 PBW EC A21 | SFK 392x236x27 G4 | SFK 392x236x27 F7 | SF 782x128x20 G4 | ||||||||||
VUT 900 PBW EC A21 | SFK 647x274x27 G4 | SFK 647x274x27 F7 | SF 647x274x20 G4 | ||||||||||
VUE 550 PBW EC A21 | SFK 392x236x27 G4 | SFK 392x236x27 F7 | SF 782x128x20 G4 | ||||||||||
VUE 900 PBW EC A21 | SFK 647x274x27 G4 | SFK 647x274x27 F7 | SF 647x274x20 G4 | ||||||||||
VUT 2000 PBW EC A21 | – | – | SF 708x480x48 G4 | ||||||||||
VUT 3000 PBW EC A21 | – | – | SF 827x741x48 G4 |
Model | Kitchen hood | Hydraulic U-trap | Silencers | Backdraft damper | Air damper | Clamps | Electric actuators | Mixing unit | ||
VUT 300 PBE EC A21 | KH-1 | SH-32 | SR 160 600/900/1200 | SRF 160 600/900/1200 | KOM 160 | KRV 160 | C 160 | LF230 | TF230 | – |
VUT 550 PBE EC A21 | SR 200 600/900/1200 | SRF 200 600/900/1200 | KOM 200 | KRV 200 | C 200 | |||||
VUT 900 PBE EC A21 | SR 250 600/900/1200 | SRF 250 600/900/1200 | KOM 250 | KRV 250 | C 250 | |||||
VUE 300 PBE EC A21 | – | SR 160 600/900/1200 | SRF 160 600/900/1200 | KOM 160 | KRV 160 | C 160 | ||||
VUE 550 PBE EC A21 | SR 200 600/900/1200 | SRF 200 600/900/1200 | KOM 200 | KRV 200 | C 200 | |||||
VUE 900 PBE EC A21 | SR 250 600/900/1200 | SRF 250 600/900/1200 | KOM 250 | KRV 250 | C 250 | |||||
VUT 2000 PBE EC A21 | SH-32 | SR 315 600/900/1200 | SRF 315 600/900/1200 | KOM 315 | KRV 315 | C 315 | ||||
VUT 3000 PBE EC A21 | SR 400 600/900/1200 | – | KOM 400 | KRV 400 | C 400 | |||||
VUT 550 PBW EC A21 | SR 200 600/900/1200 | SRF 200 600/900/1200 | KOM 200 | KRV 200 | C 200 | USWK | ||||
VUT 900 PBW EC A21 | SR 250 600/900/1200 | SRF 250 600/900/1200 | KOM 250 | KRV 250 | C 250 | |||||
VUE 550 PBW EC A21 | – | SR 200 600/900/1200 | SRF 200 600/900/1200 | KOM 200 | KRV 200 | C 200 | ||||
VUE 900 PBW EC A21 | SR 250 600/900/1200 | SRF 250 600/900/1200 | KOM 250 | KRV 250 | C 250 | |||||
VUT 2000 PBW EC A21 | SH-32 | SR 315 600/900/1200 | SRF 315 600/900/1200 | KOM 315 | KRV 315 | C 315 | ||||
VUT 3000 PBW EC A21 | SR 400 600/900/1200 | – | KOM 400 | KRV 400 | C 400 |